Circuit protection & motor control · Product family
NXM Moulded Case Circuit Breaker
CHINT NXM Moulded Case Circuit Breaker for circuit protection & motor control applications. Published details include Application: Protection against overload, short-circuit, and under-voltage; suitable for distribution and motor circuits; Frame Sizes: 63A, 125A, 160A(W125), 250A, 400A, 630A, 800A(W630), 1000A(W800), 1250A, 1600A. Ask Innovelec about selection, project requirements and availability.
Specifications
| Characteristic | Published value |
|---|---|
| Application | Protection against overload, short-circuit, and under-voltage; suitable for distribution and motor circuits Source ↗ |
| Frame Sizes | 63A, 125A, 160A(W125), 250A, 400A, 630A, 800A(W630), 1000A(W800), 1250A, 1600A Source ↗ |
| Rated Operational Voltage (Ue) | 220V / 230V / 240V / 380V / 400V / 415V / 500V / 690V Source ↗ |
| Rated Insulation Voltage (Ui) | Up to 1000V Source ↗ |
| Breaking Capacity Codes | E (15kA), S (25–36kA), F (36–50kA), H (50–70kA) Source ↗ |
| Rated Impulse Withstand Voltage (Uimp) | 8–12 kV Source ↗ |
| Utilization Category | Cat A (Thermal Magnetic) / Cat B (Electronic) Source ↗ |
| Published specification | Thermal-magnetic fixed type Source ↗ |
| Published specification | Magnetic fixed type Source ↗ |
| Published specification | Electronic type Source ↗ |
| Rated Current (In) | 16A – 1600A (depending on frame size) Source ↗ |
| Published specification | Up to 70kA at 400V AC Source ↗ |
| Published specification | Up to 50kA at 690V AC Source ↗ |
| Frequency | 50/60Hz Source ↗ |
| Number of Poles | 2P, 3P, 4P Source ↗ |
| Installation Methods | Fixed or Plug-in Source ↗ |
| Operating Temperature Range | −25°C to +70°C Source ↗ |
| Altitude Limit | ≤2000m (with derating above) Source ↗ |
| Protection Grade | IP30 (excluding terminals) Source ↗ |
| Environmental Durability | Tested for dry heat, salt mist, and humidity, compliant with IEC 60068 Source ↗ |
| Standard Compliance | IEC/EN 60947-1, IEC/EN 60947-2, IEC/EN 60947-3 Source ↗ |
| Published specification | Auxiliary & Alarm Contacts Source ↗ |
| Published specification | Motor-driven Mechanism Source ↗ |
| Published specification | Shunt & Undervoltage Release Source ↗ |
| Published specification | Interphase Barriers Source ↗ |
| Published specification | Plug-in Base and Handheld Test Module Source ↗ |
Published ranges and options describe this model or family; confirm the selected configuration for your application.
Datasheets & technical documents
- NXM-MCCB-Catalog.pdf ↗Catalog
- 2104-NXM-MCCB-Manual-2.pdf ↗Manual
- 2104-NXM-MCCB-Manual-1.pdf ↗Manual
- 2406-NXM-160-MCCB-CB Certificate.pdf ↗Certificate
- 2406-NXM-1000-MCCB-CE Certificate.pdf ↗Certificate
- 2406-NXM-1250-MCCB-CE Certificate.pdf ↗Certificate
- 2406-NXM-1600-MCCB-CB Certificate.pdf ↗Certificate
- 2406-NXM-800-MCCB-CE Certificate.pdf ↗Certificate
- 2406-NXM-800-MCCB-CB Certificate.pdf ↗Certificate
- 2406-NXM-160-MCCB-CE Certificate.pdf ↗Certificate
- 2406-NXM-1000-MCCB-CB Certificate.pdf ↗Certificate
- 2406-NXM-1250-MCCB-CB Certificate.pdf ↗Certificate
- 2405-NXM-1600-MCCB-CE Certificate.pdf ↗Certificate
- 2206-NXM-MCCB-EAC Certificate.pdf ↗Certificate
Project suitability: Global catalog range. Canadian project suitability, certification and availability must be confirmed for the selected model.
Discuss your requirements
- Application and installation environment
- Electrical ratings and required configuration
- Quantity, project location and delivery requirements
PRODUCT KNOWLEDGE FOR YOUR TEAM
Want to learn about this product?
Discuss NXM Moulded Case Circuit Breaker with Innovelec. Bring your application questions, compare options, or arrange a session for your team.
LET US HELP YOU FIND IT
Can’t find what you need?
Tell us the model, application or specifications. Our team can help identify the right product and request missing technical information.
YOUR PROJECT SHORTLIST
Quote list 0
Add products to prepare one inquiry for our team.
Your inquiry is sent only when you send the email. Include your project location, specifications and required date. You can attach drawings in your email app.