Circuit protection & motor control · Product family
NXZ(H)B
CHINT NXZ(H)B for circuit protection & motor control applications. Published details include Rated Operational Voltage (Ue): 400 V / 415 V AC 50/60 Hz; Rated Insulation Voltage (Ui): 500 V – 1000 V (depending on model). Ask Innovelec about selection, project requirements and availability.
Specifications
| Characteristic | Published value |
|---|---|
| Rated Operational Voltage (Ue) | 400 V / 415 V AC 50/60 Hz Source ↗ |
| Rated Insulation Voltage (Ui) | 500 V – 1000 V (depending on model) Source ↗ |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV Source ↗ |
| Frame Current Range | 63 A – 800 A Source ↗ |
| Rated Current Options | 16 A – 800 A (configurable per model) Source ↗ |
| Utilization Category | AC-33B (NXZHB) / AC-33iB (NXZB) Source ↗ |
| Poles | 3 P / 4 P Source ↗ |
| Rated Conditional Short-Circuit Current (Iq) | 100 kA Source ↗ |
| Control Power Supply | AC 230/240 V, 50 Hz Source ↗ |
| Control Voltage Range | 85% – 110% Ue Source ↗ |
| Operating Transfer Time | ≤ 1.4 s (standard type) Source ↗ |
| Mechanical Endurance | ≥ 10,000 operations Source ↗ |
| Electrical Endurance | ≥ 1,500 operations Source ↗ |
| Operating Temperature | −5 °C to +40 °C (optional −25 °C to +70 °C) Source ↗ |
| Altitude | ≤ 2000 m Source ↗ |
| Humidity | ≤ 90 % (at 20 °C) Source ↗ |
| Published specification | Over-voltage / under-voltage / phase-loss protection Source ↗ |
| Published specification | Fire-fighting linkage and feedback Source ↗ |
| Published specification | Generator startup and stop delay control Source ↗ |
| Published specification | Manual / automatic / remote switching modes Source ↗ |
| Communication | RS-485 interface, Modbus protocol (intelligent type only) Source ↗ |
| Mounting | Integrated or split controller; vertical / horizontal installation Source ↗ |
| Compliance | IEC 60947-1 / 60947-6-1, IEC 60068 series; CB, CE, KEMA certified Source ↗ |
Published ranges and options describe this model or family; confirm the selected configuration for your application.
Datasheets & technical documents
- 2501-NXZ(H)B、NXZ(H)M-ATSE-Catalog.pdf ↗Catalog
- 1801-NXZ(H)M NXZB-ATSE-Manual-2.pdf ↗Manual
- NXZB-63 NXZHB-63 Series(英文)0ZTD.463.1129.EN 70g双胶.pdf ↗Manual
- 2206-NXZHB-ATSE-EAC Certificate.pdf ↗Certificate
- 1801-NXZB-63S,H-ATSE-CE Certificate.pdf ↗Certificate
- 1712-NXZB-63S,H-ATSE-KEMA Certificate.pdf ↗Certificate
- 1712-NXZB-63S,H-ATSE-CB Certificate.pdf ↗Certificate
- 1709-NXZHB-63-ATSE-CB Certificate.pdf ↗Certificate
- 1709-NXZHB-63-ATSE-CE Certificate.pdf ↗Certificate
- 1708-NXZHB-63-ATSE-KEMA Certificate.pdf ↗Certificate
Project suitability: Global catalog range. Canadian project suitability, certification and availability must be confirmed for the selected model.
Discuss your requirements
- Application and installation environment
- Electrical ratings and required configuration
- Quantity, project location and delivery requirements
PRODUCT KNOWLEDGE FOR YOUR TEAM
Want to learn about this product?
Discuss NXZ(H)B with Innovelec. Bring your application questions, compare options, or arrange a session for your team.
LET US HELP YOU FIND IT
Can’t find what you need?
Tell us the model, application or specifications. Our team can help identify the right product and request missing technical information.
YOUR PROJECT SHORTLIST
Quote list 0
Add products to prepare one inquiry for our team.
Your inquiry is sent only when you send the email. Include your project location, specifications and required date. You can attach drawings in your email app.