MANUFACTURERS’ AGENTS TO THE ENERGY INDUSTRYWESTERN CANADA
Innovelec Canada

Gas handling & monitoring · Model / SKU

CA-3-039R-R501 — MultiAnalyser CA (five-in-one)

MultiAnalyser CA (five-in-one) CA-3-039R-R501. See the manufacturer’s technical data below for configuration and operating limits.

Specifications

Manufacturer-published characteristics
CharacteristicPublished value
Gas typeCA Source ↗
Sensorsmoisture Source ↗
SensorsO 2 Source ↗
SensorsNO Source ↗
SensorsNO 2 Source ↗
SensorsCO Source ↗
Featuresstorage of measuring results Source ↗
FeaturesWiFi Source ↗
Featuresgas return system Source ↗
SensorMeasuring principle | Measuring range | Measuring accuracy Source ↗
MoistureElectronic dew point measurement (capacitive) | - 60 °C to + 20 °C | ≤ ± 2 °C (at > −40 °C) ≤ ± 3 °C (at < −40 °C) Source ↗
Mol percent* O 2Optical measuring principle | 0 - 25 Mol-% | ≤ ± 0,3 Mol-% (to 12%)** ≤ ± 0,5 Mol-% (to 25%)*** Source ↗
Concentration NOElectrochemical reaction | 0 – 25 ppm | ≤ ± 2 % of measuring range Source ↗
Concentration NO2Electrochemical reaction | 0 - 20 ppm | ≤ ± 2 % of measuring range Source ↗
COElectrochemical reaction | 0 - 500 ppm | ± 2 % Source ↗
DeviceMoisture | O 2 0-25 % | NO 0-25 ppm | NO2 0-20 ppm | CO Source ↗
R201X | X Source ↗
R401X | X | X | X Source ↗
R501X | X | X | X | X Source ↗
Dimensions (W x H x D)21.18 x 10.59 x 15.98 inch ( 538 x 269 x 406 mm ) Source ↗
Weight55.12 lb ( 25 kg ) Source ↗
Inlet pressure0.2 - 35 bar Source ↗
Operating temperature14 to 122 °F ( -10 to +50 °C ) Source ↗
Ambient moisturemax. 90 % | relative moisture, non condensing Source ↗
Operating voltage85 - 264 V | AC Source ↗
Frequency47 - 63 Hz Source ↗
Number of max. measured values to be stored500 Source ↗
InterfaceUSB / LAN / WiFi Source ↗
Measuring timemax. 7 min | variable calculated by the system Source ↗
Protection classIP65 (device closed) / IP20 (device opened) Source ↗
Measuring principle of moisture sensorElectronic dew point measurement (capacitive) Source ↗
Measuring range of moisture sensor-76 to 68 °F ( -60 to +20 °C ) Source ↗
Measuring accuracy of moisture sensor??? °F ( ≤ ± 2 °C °C ) | (at > −40 °C ) Source ↗
Measuring accuracy of moisture sensor??? °F ( ≤ ± 3 °C ) | (at < −40 °C ) Source ↗
Measuring principle O 2 sensorOptical measuring principle Source ↗
Measuring range O 2 sensor0 - 25 mol % Source ↗
Measuring accuracy O 2 sensor≤ ± 0,3 mol % | (to 12%)** Source ↗
Measuring accuracy O 2 sensor≤ ± 0,5 mol % | (to 25%)*** Source ↗
Measuring principle concentration NO 2 sensorElectrochemical reaction Source ↗
Measuring range concentration NO 2 sensor0 – 25 ppm | NO Source ↗
Measuring range concentration NO 2 sensor0 - 20 ppm | NO 2 Source ↗
Measuring accuracy concentration NO 2 sensor≤ ± 2 % | of measuring range Source ↗
Measuring principle of CO sensorElectrochemical reaction Source ↗
Measuring range of CO sensor0 - 500 ppm Source ↗
Measuring accuracy of CO sensor± 2 % Source ↗

Published ranges and options describe this model or family; confirm the selected configuration for your application.

Datasheets & technical documents

Official documents linked

Discuss your requirements

  • Application and installation environment
  • Electrical ratings and required configuration
  • Quantity, project location and delivery requirements

PRODUCT KNOWLEDGE FOR YOUR TEAM

Want to learn about this product?

Discuss CA-3-039R-R501 — MultiAnalyser CA (five-in-one) with Innovelec. Bring your application questions, compare options, or arrange a session for your team.

Request an online meeting ↗Request an in-person meeting ↗Choose a preferred date and time. Our team will confirm availability.

LET US HELP YOU FIND IT

Can’t find what you need?

Tell us the model, application or specifications. Our team can help identify the right product and request missing technical information.

Ask us about a product ↗

Contact us ↗

YOUR PROJECT SHORTLIST

Quote list 0

Add products to prepare one inquiry for our team.

Your inquiry is sent only when you send the email. Include your project location, specifications and required date. You can attach drawings in your email app.

Contact us ↗

THE NEXT CONNECTION STARTS WITH YOU

Let’s talk about
your next project.

Connect with our team ↗