Docking & transfer switches · Product family
Generator Docking Stations
Trystar Generator Docking Stations for docking stations applications. Ask Innovelec about selection, project requirements and availability.
Specifications
| Characteristic | Published value |
|---|---|
| Electrical | Ampacity: 100A – 5000A Voltage Options: 120/240V, 120/240V Delta, 208Y/120V, 480V, 480Y/277V, 600V Frequency: 60Hz (50Hz optional) Interrupt Rating: 65kAIC – 100kAIC Breakers: 3-Pole, 4-Pole, or Single Phase Source ↗ |
| Environmental | Operating Temperature: 32°F to 104°F (0°C to 40°C) Humidity Rating: 5% – 95% RH (non-condensing) Compliance: ETL, UL 1008, UL 50 Source ↗ |
| Mechanical | Enclosure Types: NEMA 3R (powder-coated aluminum), NEMA 4X (304 or 316 stainless steel) Bus Bar: Silver-plated copper / Tin-plated copper (for wastewater applications) Source ↗ |
| Enclosure Dimensions (H × W × D) | Padmount Options: – Dual Padmount: 84” × 96.5” × 43” – Deluxe Padmount: 90” × 78.5” × 43” – Padmount Extra Depth: 84” × 48” × 61” – Padmount: 84” × 48” × 43” Wall-Mount Options: – Large Wall-Mount: 60” × 48” × 19.5” – Medium Wall-Mount: 54” × 40” × 16.5” – Small Wall-Mount: 48” × 30” × 16.5” Flange Options: – Large Flange: 78” × 52” × 21.3” – Medium Flange: 70” × 44” × 18.3” – Small Flange: 64” × 34” × 18.3” Source ↗ |
Published ranges and options describe this model or family; confirm the selected configuration for your application.
Datasheets & technical documents
- 100-300 Amp Commercial Grade Generator Docking Station Installation, Operation and Maintenance Manual ↗Manual
- 100-4000 Amp Generator Docking Station ETL 1008 Listed Installation, Operation and Maintenance Manual ↗Manual
- 100-600 Amp ETL Listed Generator Docking Station Installation, Operation and Maintenance Manual ↗Manual
- 100-800 Amp Generator Docking Station Installation, Operation and Maintenance Manual ↗Manual
- 800-4000 Amp Generator Docking Station Installation, Operation and Maintenance Manual ↗Manual
- 800-5000 Amp Generator Docking Station Installation, Operation and Maintenance Manual ↗Manual
- Generator Roll Up Box (GRUB) Docking Stations Installation, Operation and Maintenance Manual ↗Manual
- Horizontal Generator Docking Station Installation, Operation and Maintenance Manual ↗Manual
- Retail Generator Docking Station Installation, Operation and Maintenance Manual ↗Manual
- Single Breaker Generator Docking Station Installation, Operation and Maintenance Manual ↗Manual
- Data Center Brochure ↗Brochure
- Disaster Recovery Brochure ↗Brochure
- Docking Station Enclosure Sizing Guide ↗Technical document
- Single Purpose Docking Station One-Line Drawings ↗Drawing
- Generator Docking Station Handout ↗Technical document
- Generator Docking Station Spec Sheet ↗Specification
- NOTICE: NEC CODE CHANGE 700.3 ↗Technical document
- Single Purpose Docking Station (Generator) Data Sheet ↗Technical document
- Single Purpose Docking Station Parts Builder ↗Technical document
Discuss your requirements
- Application and installation environment
- Electrical ratings and required configuration
- Quantity, project location and delivery requirements
PRODUCT KNOWLEDGE FOR YOUR TEAM
Want to learn about this product?
Discuss Generator Docking Stations with Innovelec. Bring your application questions, compare options, or arrange a session for your team.
LET US HELP YOU FIND IT
Can’t find what you need?
Tell us the model, application or specifications. Our team can help identify the right product and request missing technical information.
YOUR PROJECT SHORTLIST
Quote list 0
Add products to prepare one inquiry for our team.
Your inquiry is sent only when you send the email. Include your project location, specifications and required date. You can attach drawings in your email app.