Emergency lighting · Model / series
TrueLITE Model ELS (58.5kW - 112.5kW) Three Phase
Trystar TrueLITE Model ELS (58.5kW - 112.5kW) Three Phase for emergency lighting inverters applications. Published details include Input / Output Voltage: 480/277 VAC, three-phase (wye), 60 Hz 480 VAC, three-phase (delta), 60 Hz (when output neutral not required); Input Voltage Range: +15% to –10% at full load without battery usage +15%, –30% tolerance (load dependent or with battery assistance). Ask Innovelec about selection, project requirements and availability.
Specifications
| Characteristic | Published value |
|---|---|
| Input / Output Voltage | 480/277 VAC, three-phase (wye), 60 Hz 480 VAC, three-phase (delta), 60 Hz (when output neutral not required) Source ↗ |
| Input Voltage Range | +15% to –10% at full load without battery usage +15%, –30% tolerance (load dependent or with battery assistance) Source ↗ |
| Input Frequency | 57 Hz – 63 Hz Source ↗ |
| Input Power Factor | 0.99 at nominal voltage and 25%–100% load with battery charging Source ↗ |
| Input Current Harmonics | ≤ 3% THD at 100% load Source ↗ |
| Power Walk-In | 0–30 seconds (programmable) Source ↗ |
| Output Voltage Regulation | ± 1% with balanced load ± 3% with 100% unbalanced load Source ↗ |
| Output Frequency | ± 0.05% while in battery operation mode Source ↗ |
| Output Voltage Distortion | ≤ 2% THD (linear load) ≤ 3% THD (non-linear load) Source ↗ |
| Overload Capability | 110% for 60 minutes 125% for 10 minutes 150% for 1 minute Source ↗ |
| LED Inrush Rating | Peak overload capability of 1200% , accommodating LED fixture inrush (without static bypass) Source ↗ |
| Efficiency | On-Line Mode: 93% ECO / Smart Active Modes: up to 98.5% Source ↗ |
| Operating Temperature | UL 924 “Emergency Lighting and Power Equipment” & C-UL CSA C22.2 No. 141-15: 20°C – 30°C UL 924 “Auxiliary Lighting and Power Equipment”: 0°C – 40°C Source ↗ |
| Battery Performance | Optimum battery performance and life at 25°C Source ↗ |
| Battery Runtime | UL 924: 90 minutes at full-rated kW Optional: 30, 60, 120 minutes C-UL: 30, 60, or 90 minutes Source ↗ |
Published ranges and options describe this model or family; confirm the selected configuration for your application.
Datasheets & technical documents
- Canada Code Compliance Addendum for Egress Lighting Solutions Brochure Addendum ↗Brochure
- Data Center Brochure ↗Brochure
- Emergency Lighting Inverters Brochure ↗Brochure
- TrueLite Model ELS Centralized Emergency Lighting Inverter ↗Technical document
- Design Flexibility of Inverters ↗Technical document
- Egress Lighting Integrity Test ↗Technical document
- Local Control Override ↗Technical document
- UL924 Aux Lighting and Power ↗Technical document
- Zone Sensing ↗Technical document
- Model ELS General Specification ↗Specification
- TrueLITE Model ELS(58.5kW – 112.5kW) Three Phase Owners Manual ↗Manual
Discuss your requirements
- Application and installation environment
- Electrical ratings and required configuration
- Quantity, project location and delivery requirements
PRODUCT KNOWLEDGE FOR YOUR TEAM
Want to learn about this product?
Discuss TrueLITE Model ELS (58.5kW - 112.5kW) Three Phase with Innovelec. Bring your application questions, compare options, or arrange a session for your team.
LET US HELP YOU FIND IT
Can’t find what you need?
Tell us the model, application or specifications. Our team can help identify the right product and request missing technical information.
YOUR PROJECT SHORTLIST
Quote list 0
Add products to prepare one inquiry for our team.
Your inquiry is sent only when you send the email. Include your project location, specifications and required date. You can attach drawings in your email app.